Installation manual
CF3-D, CF3-D-Disp
Figure 1 The sensor
General
The IAQ-sensor product CF3-D (for mounting in ventilation ducts) is designed to
measure carbon dioxide (CO
2
). Option - TR is prepared for temperature
measurements by the resistive temperature probe mounted by the user. Option -Disp
displays the measured CO
2
value in ppm (parts-per-million) on the LCD.
The units are designed for connecting to Direct Digital Control (DDC) with 0-10V or
2-10V signal inputs. The two parallel signal outputs Out(1) (0-10V) and Out(2) (2-10V
or 4-20 mA) give linear signal voltages or currents corresponding to the measuring
range.
The output OUT(2) also indicates the status by setting the output voltage to 1V or the
output current to 2 mA when the sensor self-diagnostics detects any error.
Vedere la pagina 0
1 2 3 4 5 6 7

Sommario

Pagina 1 - CF3-D, CF3-D-Disp

Dokument IMA 204 Rev 2 Page 1 (7) Installation manual CF3-D, CF3-D-Disp Figure 1 The sensor General The IAQ-sensor product CF3-D (for

Pagina 2

Dokument IMA 204 Rev 2 Page 2 (7) 1212345679810 Figure 2 Parts of the CF3-D for duct mounting 1 Sampling probe 6 O-ring 29,2x3,53 (Factor

Pagina 3 - Mounting Instruction

Dokument IMA 204 Rev 2 Page 3 (7) Mounting of CF3-D on to the duct. Figure 3 Mounting of the sensor to the ventilation duct 10 Hole with 25

Pagina 4 - Electrical connections

Dokument IMA 204 Rev 2 Page 4 (7) Electrical connections The power supply has to be connected to and . is considered as system ground.

Pagina 5 - Self-diagnostics

Dokument IMA 204 Rev 2 Page 5 (7) Figure 4 PCB with jumper to configure OUT2 for current output 4-20mA or voltage output 2-10VDC Figure 5 E

Pagina 6 - Maintenance

Dokument IMA 204 Rev 2 Page 6 (7) Maintenance The CF3-D is basically maintenance free in normal environments thanks to the built-in self-co

Pagina 7 - Dimensions

Dokument IMA 204 Rev 2 Page 7 (7) Dimensions Figure 7 The dimensions of the sensor in mm and (inches)